Setting Tag Data Links
5. In the Name Field, enter the character string for the CPU Unit's I/O memory
6. Input the size of the tag in the Size Field, in bytes.
7. Click the Regist Button to register the tag.
8. Click the Out - Produce Tab, and click the New Button. The Edit Tag Dialog
address or a network symbol (e.g., 100, W100, D0, Input_signal).
Addresses in the following I/O memory areas can be set.
Note (a) The H, W, D, and E characters can also be input in lower case as
If an I/O memory address is specified for a tag name, the Edit Tags Dialog
Box will be displayed with the next consecutive address as the tag name
for editing the next tag. Once you have registered the tags, click the Cancel
Button.
Box will be displayed, like the dialog box for input tags, except for the Over
Load setting. The Over Load setting determines whether outputs are
cleared or continue their previous status when outputs are turned OFF with
the PLC’s Output OFF function. Output inhibit settings are not required for
input (reception) tag sets.
CIO Area
Holding Area
Work Area
DM Area
EM Area
• Follow the output inhibit function: Enabled (default)
• Do not follow the output inhibit function: Disabled
Output data is cleared to 0 when a PLC output inhibit occurs.
Output data maintains its previous status even after a PLC output in-
hibit occurs.
(b) Be sure to directly enter the CPU Unit's I/O memory address
CPU Unit’s data area
h, w, d, and e.
(e.g., 100, W100, D0) or a network symbol as a character string.
Bank 0 hex E0_00000 to E0_32767
Bank 18
hex
0000 to 6143
H000 to H511
W000 to W511
D00000 to D32767
E18_00000 to E18_32767
Address (Text to input in Name Field.)
Section 6-2
129