Switching Hub Installation Environment Precautions
Switching Hub Connection Methods
42
Network Installation
Note
Note Adjust the link settings of the EtherNet/IP Unit or built-in EtherNet/IP port to
Connect two hubs to each other as follows: Connect an MDI port to an MDI-X
port with a straight cable; connect two MDI ports with a cross cable; and
connect two MDI-X ports with a cross cable.
It is very difficult to distinguish cross cables and straight cables by appear-
ance. Incorrect cables will cause communications to fail. We recommend
using cascade connections with straight cables whenever possible.
Some switching hubs can automatically distinguish between MDI and MDI-X.
When this kind of switching hub is being used, straight cable can be used
between switching hubs.
match the communications settings of the connected switching hub. If the set-
tings do not match, the link will become unstable and prevent normal commu-
nications. The following table shows the allowed settings for each switching
hub communications mode.
Auto-negotiation
10 Mbps
(fixed)
• Press the cable connector in firmly until it locks into place at both the
• Do not lay the twisted-pair cable together with high-voltage lines.
• Do not lay the twisted-pair cable near devices that generate noise.
• Do not lay the twisted-pair cable in locations subject to high temperatures
• Do not lay the twisted-pair cable in locations subject to excessive dirt and
• Do not ground the switching hub in the same location as a drive-system
• Always use a dedicated power supply for the switching hub’s power sup-
• Before installation, check the switching hub’s environment-resistance
Switching hub setting
switching hub and the EtherNet/IP Unit.
or high humidity.
dust or to oil mist or other contaminants.
component such as an inverter.
ply. Do not use the same power supply used for other equipment, such as
an I/O power supply, motor power supply, or control power supply.
specifications, and use a switching hub appropriate for the ambient condi-
tions. Contact the switching hub manufacturer for details on switching
hub’s environment-resistance specifications.
MDI-X port
(cross)
Full duplex
Half duplex OK
Switching
Hub
MDI ports
Best
---
negotiation
Auto-
Switching
Hub
---
OK
---
EtherNet/IP Unit setting
duplex
10 Mbps (fixed)
Full
Switching
Hub
Straight cable
Cross cable
OK
---
OK
duplex
Half
---
---
---
duplex
100 Mbps (fixed)
Full
Switching
Hub
Section 3-4
OK
---
---
duplex
Half