CJ1W-EIP21 Omron, CJ1W-EIP21 Datasheet - Page 390

no-image

CJ1W-EIP21

Manufacturer Part Number
CJ1W-EIP21
Description
Ethernet I/P Module
Manufacturer
Omron
Datasheet

Specifications of CJ1W-EIP21

Lead Free Status / Rohs Status
Lead free / RoHS Compliant
Connection Status Codes and Error Processing
362
01
01
08
D0
D0
General
Connection status
Status
(hex)
0316
031C
---
0001
0002
Additional
Status
(hex)
Error code returned from target:
There was a parameter error in
the frame used to close the con-
nection.
Error code generated in origina-
tor:
Some other error occurred.
Error code returned from target:
There is no Forward Open or
Large Forward Open service in
the target device.
Error code generated in origina-
tor:
The connection operation is
stopped.
Error code generated in origina-
tor:
The connection is being opened
(opening processing in
progress).
Source of error
This error does
not occur.
This error does
not occur.
This error does
not occur.
The connection
was stopped
because the Tag
Data Link Stop Bit
was turned ON, or
the settings data
is being down-
loaded.
Either turn ON the
Tag Data Link
Start Bit, or wait
until the settings
data has been
downloaded.
Includes Control-
ler stop errors,
Unit failure, and
EM bank files at
the refresh desti-
nation. To handle
these errors, refer
to 14-2-1Errors
Occurring at the
EtherNet/IP Unit
or built-in Ether-
Net/IP port.
Wait until the
opening process-
ing is completed.
Configuration 1
Depends on the tar-
get’s specifications.
(Contact the target
device’s manufac-
turer.)
The originator gener-
ates this code when
an unsupported
response code is
returned from the
target in reply to a
connection-opening
request.
Depends on the tar-
get’s specifications.
(Contact the target
device’s manufac-
turer.)
The meaning of this
error code is defined
by each vendor, so it
depends on the tar-
get’s specifications.
(Contact the target
device’s manufac-
turer.)
The meaning of this
error code is defined
by each vendor, so it
depends on the tar-
get’s specifications.
(Contact the target
device’s manufac-
turer.)
Configuration 2
Handling
Depends on the orig-
inator’s specifica-
tions. (Contact the
originator device’s
manufacturer.)
Depends on the orig-
inator’s specifica-
tions. (Contact the
originator device’s
manufacturer.)
Depends on the orig-
inator’s specifica-
tions. (Contact the
originator device’s
manufacturer.)
Depends on the orig-
inator’s specifica-
tions. (Contact the
originator device’s
manufacturer.)
Depends on the orig-
inator’s specifica-
tions. (Contact the
originator device’s
manufacturer.)
Configuration 3
Section 14-3

Related parts for CJ1W-EIP21