Network Installation
3-4
3-4-1
3-4-2
3-4-3
Precautions on Laying Twisted-pair Cable
Network Installation
Basic Installation Precautions
Recommended Products
Precautions
Note The maximum current consumption of the CS1W-EIP21 and CJ1W-EIP21
EtherNet/IP Units is 410 mA. Be sure that the total current consumption of all
the Units connected to the same CPU Backplane or Expansion Backplane
does not exceed the output capacity of the Power Supply Unit.
The following table shows the devices recommended for use with the Ether-
Net/IP Unit 2-3 Selecting the Network Devices.
• Take the greatest care when installing the Ethernet System, being sure to
• Do not install Ethernet equipment near sources of noise. If a noisy envi-
• When installing an EtherNet/IP network that combines an information sys-
• Noise resistance may be reduced by ground loops, which can occur due
• Do not connect the shield to the EtherNet/IP Unit’s connector.
• If a cable connects two hubs, connect the shields at only one end.
follow ISO 8802-3 specifications. You must obtain a copy of these specifi-
cations and be sure you understand them before attempting to install an
Ethernet System. Unless you are already experienced in installing com-
munications systems, we strongly recommend that you employ a profes-
sional to install your system.
ronment is unavoidable, take adequate measures against noise interfer-
ence, such as installing network components in grounded metal cases or
using optical cable in the system.
tem with the control system, and the communications load may be heavy
due to tag data links, we recommend configuring the network so that the
load does not affect communications. For example, install the tag data
links in a segment that is separate from the information network.
to improper shield connections and grounding. Ground the shield at one
location, as shown in the following diagram.
GR
Connector
Hub
Connector
(Shield)
STP
GR
Connector
Hub
Connector
Connector
(Shield)
(Shield)
STP
STP
Connect shield.
Do not connect shield.
Connector
Connector
Unit
Unit
EIP
EIP
terminal
terminal
Supply
Supply
Power
Power
Unit
Unit
Section 3-4
GR
GR
41