CJ1W-EIP21 Omron, CJ1W-EIP21 Datasheet - Page 363

no-image

CJ1W-EIP21

Manufacturer Part Number
CJ1W-EIP21
Description
Ethernet I/P Module
Manufacturer
Omron
Datasheet

Specifications of CJ1W-EIP21

Lead Free Status / Rohs Status
Lead free / RoHS Compliant
Restoring the EtherNet/IP
Unit or Built-in EtherNet/IP
Port Setup File from the
Memory Card
(Reading and Setting the
Data in the Unit)
Simple Backup Function
Note
Note
This operation will create an EtherNet/IP Unit or built-in EtherNet/IP port set-
tings file, and write that file to the Memory Card along with the other backup
files. When the Memory Card Power Supply Switch is pressed, the MCPWR
indicator on the front of the CPU Unit will flash once and then remain lit while
data is being written. If the data is written normally, the MCPWR indicator will
turn OFF. The BUSY indicator will flash while the data is being written.
The backup operation will fail if it is performed after the device parameters
were not downloaded successfully from the Network Configurator or CX-Pro-
grammer. Perform the backup operation only if the device parameters were
downloaded normally.
Set pins 7 and 8 of the DIP switch on the front panel of the CPU Unit, as
shown in the following table, and turn the power to the CPU Unit OFF and
then ON again with the Memory Card inserted into the slot.
This operation will read the EtherNet/IP Unit or built-in EtherNet/IP port setup
data file from the Memory Card and restore the data in the EtherNet/IP Unit or
built-in EtherNet/IP port.
When the power supply is ON, the MCPWR indicator on the front of the CPU
Unit will turn ON, flash once, and then remain lit while data is being read. The
BUSY indicator will flash while data is being read. After the data has been
read correctly, the MCPWR and BUSY indicators will turn OFF. If the MCPWR
indicator flashes five times or if only the BUSY indicator turns OFF, it means
that an error has occurred.
If the restoration from the Memory Card fails, an “H8” error will be displayed
on the 7-segment display on the front panel. If this happens, the data on the
Memory Card may not be correct. Confirm that the backup operation was
completed normally before performing the restore operation.
SW7
SW8
EtherNet/IP Unit
EtherNet/IP Unit
All setup data
All setup data
DIP switch settings
ON
OFF
Power ON
Backup
Restore
CPU Unit
CPU Unit
All data
All data
Memory Card
Memory Card
Memory Card
Power Supply Switch
Section 13-2
335

Related parts for CJ1W-EIP21