Connection Status Codes and Error Processing
360
01
01
01
01
01
01
01
01
General
Connection status
Status
(hex)
0109
0110
0111
0113
0114
0115
0116
0117
Additional
Status
(hex)
Error code returned from target:
The connection size settings
are different in the originator
and target.
Error code returned from target:
The target was unable to open
the connection, because of its
operating status, such as down-
loading settings.
Error code returned from target:
The RPI was set to a value that
exceeds the specifications.
Error code generated by origi-
nator or returned from target:
Attempted to open more con-
nections than allowed by the
specifications (CJ2M-EIP21:
32, other CPU Units: 256).
Error code returned from target:
The Vendor ID and Product
Code did not match when open-
ing connection.
Error code returned from target:
The Product Type did not match
when opening connection.
Error code returned from target:
The Major/Minor Revisions did
not match when opening con-
nection.
Error code returned from target:
The tag set specified in the con-
nection’s target variables does
not exist.
Source of error
Check the connection sizes set in the originator and target.
Check whether
the tag data link is
stopped at the tar-
get. (Restart the
tag data link com-
munications with
the control bit.)
This error does
not occur.
Check the con-
nection settings
(number of con-
nections) at the
originator and tar-
get.
This error does
not occur.
This error does
not occur.
Check the major
and minor revi-
sions set for the
target device and
connection. If nec-
essary, obtain the
EDS file and set it
again.
Check whether
the originator and
target tag sets
and tags are set
correctly.
CJ2 CPU Units
Only: Check sym-
bol settings in the
CPU Unit.
Configuration 1
Depends on the tar-
get’s specifications.
(Contact the target
device’s manufac-
turer.)
Check the target’s
RPI setting specifica-
tions.
Check the connec-
tion settings (number
of connections) at
the originator and
target.
Check the connec-
tion specifications for
another company’s
devices.
Depends on the tar-
get’s specifications.
(Contact the target
device’s manufac-
turer.)
Confirm that the tar-
get device’s EDS file
is correct.
Depends on the tar-
get’s specifications.
(Contact the target
device’s manufac-
turer.)
Confirm that the tar-
get device’s EDS file
is correct.
Depends on the tar-
get’s specifications.
(Contact the target
device’s manufac-
turer.)
Confirm that the tar-
get device’s EDS file
is correct.
Depends on the tar-
get’s specifications.
(Contact the target
device’s manufac-
turer.)
Configuration 2
Handling
Check whether the
tag data link is
stopped at the origi-
nator. (Restart the
tag data link commu-
nications with the
control bit.)
Set the originator’s
RPI setting to 10
seconds or less.
Check the connec-
tion settings (number
of connections) at
the originator and
target.
Check the connec-
tion specifications for
another company’s
devices.
Check the origina-
tor’s connection set-
tings.
Check the origina-
tor’s connection set-
tings.
Check the origina-
tor’s connection set-
tings.
Check the origina-
tor’s connection set-
tings. Check whether
the target’s tag sets
and tags are set cor-
rectly.
CJ2 CPU Units Only:
Check symbol set-
tings in the CPU
Unit.
Configuration 3
Section 14-3