Procedure for Using FINS/TCP
FINS/TCP Method
1,2,3...
Note
Note
After a connection has been established as a FINS/TCP client, it can be termi-
nated in the following ways.
Even if the connection is closed at the FINS/TCP client, requests continue to
be made to the FINS/TCP server every few seconds to open a connection.
After the EtherNet/IP Unit or built-in EtherNet/IP port is powered up or
restarted, the IP address for the connection used as the FINS/TCP client is
the remote IP address that was set in the FINS/TCP Tab Page of the CX-Pro-
grammer’s Edit Parameters Dialog Box. To dynamically change the remote IP
address (i.e., during CPU Unit operation), execute the CMND(490) instruction
in the ladder program and send a FINS command (FINS/TCP CONNECTION
REMOTE NODE CHANGE REQUEST; command code: 27 30 hexadecimal)
to the EtherNet/IP Unit or built-in EtherNet/IP port.
1. Make the basic settings.
2. Make the following settings on the FINS/TCP Tab Page of the CX-Pro-
3. Select Transfer to PLC from the PLC Menu and click the Yes Button. The
4. Make the routing table settings and transfer them to each PLC. (See note
5. Create a ladder program that includes the SEND(090), RECV(098), and
(1) Routing tables are required in the following situations:
• If the connection is closed by the server.
• If there is no response from the client when the keep-alive function is in
effect.
Refer to Initial Settings in 3-1-1 Procedures.
grammer's Edit Parameters Dialog Box.
setting data will be transferred to the CPU Bus Unit System Setup Area in
the CPU Unit.
1.)
Set the routing tables with CX-Integrator, and transfer it to each PLC.
CMND(490) instructions.
• FINS/TCP port (default: 9600)
• Server/Client: Specifies whether the connection will operate in FINS/
• Target IP address for client: Specifies the IP address of the target
• Target IP address for server: Specifies allowed client IP addresses
• Automatically allocated FINS node address for server: Specifies the
• Keep-alive: Specified whether to use the keep-alive function.
• Enable protect via IP address:
• When communicating with a PLC or computer on another network
• When multiple Communications Units are mounted to a single PLC
TCP server mode or client mode.
FINS/TCP server.
when protection is enabled.
address to allocate when automatically allocating a FINS node ad-
dress to the target FINS/TCP client.
Note Normally this function is used and the option is selected.
Note Select this option only when protecting as the server.
(e.g., remote programming or monitoring using FINS messages or a
CX-Programmer)
(i.e., CPU Unit)
Section 8-3
205