Troubleshooting with FINS Response Codes
372
01
02
03
04
05
Main response
Value and
meaning
Local node
error
Remote
node error
Unit error
(Controller
error)
Service not
supported
Routing
error
code
03
05
07
01
02
05
01
02
04
01
01
02
03
04
Sub response code
Value and meaning
Local node send
error
Node address set-
ting error
Local node busy
(send failed)
Remote node not in
network
No Unit with speci-
fied unit address
Response timeout
Communications
controller error
PLC error
Unit number setting
error
Unsupported com-
mand
Routing table setting
error
Routing tables not
registered
Routing table error
Too many relay
points
---
Local IP
address
System load
IP address
table and IP
router table
Instruction’s
control data
Transfer condi-
tions
(Use FINS
status read
commands.)
Instruction’s
control data
Read the error
log.
Affected con-
troller’s ERC
indicator
Affected
node’s LED
indicators
Unit number
Command
code
FINS header
frame length
Routing tables Remote node is not set in
Routing tables Destination is unknown
Routing tables Routing table error
Network con-
figuration
Item to check
Lack of available space in
internal buffers
The network cannot be
used because the IP
address setting is incor-
rect.
Lack of available space in
internal buffers
IP address of remote
node not set correctly.
There is no Unit with the
specified unit address.
Message packet was cor-
rupted by transmission
error.
The response monitoring
time is too short.
The transmission frame
may be corrupted or the
internal reception buffer
full.
Error occurred in the
communications control-
ler.
CPU Unit error occurred
in the PLC at the remote
node.
The unit number setting
is incorrect.
The specified command
code is not supported by
the destination Unit.
A short frame (4 bytes) is
being used for the FINS
header frame.
the routing tables.
because there are no
routing tables.
The maximum number of
network levels (3) was
exceeded in the com-
mand.
Likely cause
The load (traffic) on the Ether-
net Unit is too heavy. Check
your user applications.
Correct the local IP address.
The load (traffic) on the Ether-
net Unit is too heavy. Check
your user applications.
Set IP address of remote
node into IP address table
and, if internetwork transmis-
sion is required, into the IP
router table.
Check the remote node's unit
address.
Increase the number of trans-
mit retry attempts.
Set a longer response moni-
toring time.
Read out the error log and
correct the system as
required.
Take corrective action, refer-
ring to troubleshooting proce-
dures in this section.
Clear the error in the CPU
Unit. (Refer to the PLC's oper-
ation manuals.)
Confirm that the unit number
set on the switch is within the
specified range and that the
same unit number is not used
twice in the same network.
Check the command code.
The EtherNet/IP Unit does not
support short headers.
Set the destination address in
the routing tables.
Set routing tables at the local
node, remote node, and any
relay nodes.
Set the routing tables cor-
rectly.
Redesign the network, or
reconsider the routing tables
to reduce the number of relay
nodes in the command.
Corrective action
Section 14-6