6-2-8
Setting Tag Data Links
Creating Connections by Device Dragging and Dropping
1,2,3...
Note
You can create a connection to the originator by dragging a target device and
dropping it at the originator device. Network Configurator version 3.10 or
higher is required to drag and drop devices to make connections.
The EtherNet/IP originator device (i.e., a device in which connections can be
set) must be one of the following OMRON EtherNet/IP devices.
Use the following procedure to create connections (i.e., data links) by drag-
ging and dropping devices.
1. Set the tags and tag sets for the target device that will be dragged.
2. A dialog box as in the following figure for connection allocation will be dis-
CJ1W-EIP21
CJ1W-EIP21(CJ2)
CJ2B-EIP21
CJ2M-EIP21
CS1W-EIP21
Example:
a. Refer to 6-2-4 Creating Tags and Tag Sets for information on creating
b. If the target is another EtherNet/IP device, refer to the manual of that
played when you drag the target device and drop it at the OMRON Ether-
Net/IP device.
a. Using One of the Above OMRON EtherNet/IP Devices As Target
Device name
Drag & Drop
the settings if the target is one of the OMRON EtherNet/IP devices giv-
en above.
device and perform settings as required.
Select the output tag set from Target Device Area on the right side of
the Edit Connection Dialog Box, and then select the input tag set to re-
ceive the output tag set in the Originator Device Area on the left.
Drag the target device at 192.168.250.1 and drop it at the orig-
inator device at 192.168.250.100.