Datasheet

Specifications of CJ1W-EIP21

Lead Free Status / Rohs Status
Lead free / RoHS Compliant
user
Format
Function
ls
Format
Function
dir
Format
Function
rename
Format
Function
Using FTP Commands
user [user_name]
Specifies the user name. Specify the FTP login name set in the EtherNet/IP
Unit or built-in EtherNet/IP port system setup. The default FTP login name is
“CONFIDENTIAL.”
If a non-default login name is used, it must be followed by the password. In
this case, enter the FTP password set in the system setup.
The user name is automatically requested immediately after connection to the
FTP server.
ls [-l] [REMOTE_FILE_NAME [local_file_name]]
Displays the remote host (Memory Card or EM File Memory) file names.
Set the switch [-l] to display not only the file names but the creation date and
size as well. If the switch is not set, only the file names will be displayed.
You can specify a file name in the Memory Card or EM File Memory if desired.
If a local file name is specified, the file information will be stored in the speci-
fied file in the host computer.
dir [REMOTE_FILE_NAME [local_file_name]]
Displays the file names, date created, and size of the files in the remote host
(Memory Card or EM File Memory). It displays the same information as com-
mand [ls -l].
Specify a file name in the Memory Card or EM File Memory as the remote file
name.
If a local file name is specified, the file information is stored in the specified file
in the host computer.
rename CURRENT_FILE_NAME NEW_FILE_NAME
Changes the specified current file name to the specified new file name.
rename can be used only to change the file name. It cannot be used to move
the file to a different directory.
Section 11-5
309