14-5-5 Message Timeout Problems
14-6 Troubleshooting with FINS Response Codes
Troubleshooting with FINS Response Codes
00
Main response
Value and
meaning
Normal
completion
code
00
Sub response code
Value and meaning
---
The cause of errors that occur when using the SEND(090), RECV(098), or
CMND(490) instructions can be identified from the response codes. (Refer to
the description of Communications Port Completion Codes in 8-6-4 Writing
Programs for the storage locations of response codes generated by the
SEND(090), RECV(098), or CMND(490) instructions.)
This section describes the completion codes produced by EtherNet/IP Units.
For details on completion codes produced by CPU Units, other CPU Bus
Units, or computers equipped with FINS services, refer to the device’s opera-
tion manual.
The 6
6
node; the 7
remote node; and the 15
occurred. The following table explains the meaning of the completion codes.
Bit
Timeout errors
occur frequently in
message services
(CIP UCMM, CIP
Class 3, or FINS).
th
Relay Error Flag
bit will be ON when a non-fatal error has occurred in the PLC at the remote
7
th
6
Main response code (RES)
, 7
5
PLC Fatal Error Flag
th
First byte
4
---
Item to check
, and 15
th
bit will be ON when a fatal error has occurred in the PLC at the
3
2
1
th
• When there is a high load in the tag data link, and the CPU
• In this case, the communications load must be reduced by
• The tag data link’s bandwidth usage can be checked on the
• The error log error codes that indicate discarded messages
• For information on preventing high loads in FINS communi-
0
bits of the response codes have specific functions. The
Unit’s cycle time is relatively long or there are messages
coming in from many nodes, the message service response
time may be delayed and messages may be discarded occa-
sionally.
increasing (slowing) the tag data link’s RPI, reducing the
message load, or increasing the timeout value.
Monitor Device Window’s Ethernet Information Tab Page.
Refer to 14-1 Checking Status with the Network Configurator
for details.
(insufficient memory) due to heavy communications loads
are 0117, 0119, 0123, 0125, 03C2 (detail code @@08,
@@09, or @@0A), 03C3, and 03D2. Refer to 14-1 Checking
Status with the Network Configurator for details on reading
the error codes on the Error History Tab Page.
cations, refer to 8-7 Precautions on High Traffic in FINS
Communications.
7
---
th
6
PLC Non-fatal Error Flag
bit will be ON when a network relay error has
5
Sub response code (SRES)
Second byte
Likely cause
4
3
2
1
0
---
Corrective action
Section 14-6
371