CJ1W-EIP21 Omron, CJ1W-EIP21 Datasheet - Page 275

no-image

CJ1W-EIP21

Manufacturer Part Number
CJ1W-EIP21
Description
Ethernet I/P Module
Manufacturer
Omron
Datasheet

Specifications of CJ1W-EIP21

Lead Free Status / Rohs Status
Lead free / RoHS Compliant
Sending Explicit Messages
Program Example
000000
000013
000018
000024
First Cycle Flag
Execution
condition
A20011
000000
000001
Communications
Enabled Flag
Communications
Enabled Flag
A20200
A20200
A21900
Network Communication
Execution Error Flag
151100
Online Flag
(n+11, bit 00)
BSET #0000 D00000 D02999
CMND D01000 D02000 D00000
(071)
(490)
MOV #0028 D00000
MOV #0064 D00001
MOV #0001 D00002
MOV #0510 D00003
MOV #0000 D00004
MOV #00A0 D00005
MOV A203
MOV #2810 D1000
MOV #0000 D1001
MOV #05DC D1002
MOV #5202 D1003
MOV #2006 D1004
MOV #2401 D1005
MOV #0A0C D1006
MOV #0600 D1007
MOV #0102 D1008
MOV #2001 D1009
MOV #2401 D1010
MOV #0800 D1011
MOV #120D D1012
MOV #3139 D1013
MOV #322E D1014
MOV #3136 D1015
MOV #382E D1016
MOV #3235 D1017
MOV #302E D1018
MOV #3200 D1019
(021)
(021)
(021)
(021)
(021)
(021)
(021)
(021)
(021)
(021)
(021)
(021)
(021)
(021)
(021)
(021)
(021)
(021)
(021)
(021)
(021)
(021)
(021)
(021)
(021)
(021)
(021)
(021)
MOV #0001 0000
ASR 0000
ASL 0000
(025)
(026)
D00006
END
(001)
Moves 0001 into CIO 0000.
Sets 0000 in D00000 to D02999.
Sets 0028 in D00000. (Number of send data bytes: 40)
Sets 0064 in D00001. (Number of receive data bytes: 100).
Sets 0001 in D00002. (Destination network address: 01).
Sets 0510 in D00003. (Destination node address: 05, destination unit address: 10)
Sets 0000 in D00004.
(Response required, port number 0, number of retries = 0)
Sets 00A0 in D00005. (Response monitoring time: 16.0 s)
Sends 8 bytes of command data to destination node address 06, receives
14 bytes of response data, and stores it in the local node starting at D02000.
(D00000 is control data.)
Shifts the contents of CIO 0000 one bit to the left.
Copies the completion code (network communications error response code)
from A203 to D00006.
Shifts the contents of CIO 0000 one bit to the right and
retries in the next cycle (CIO 000000 ON).
Command data
Set the CIP UCMM MESSAGE SEND command's command data
in words D01000 to D01019 in routing data format.