CJ1W-EIP21 Omron, CJ1W-EIP21 Datasheet - Page 53

no-image

CJ1W-EIP21

Manufacturer Part Number
CJ1W-EIP21
Description
Ethernet I/P Module
Manufacturer
Omron
Datasheet

Specifications of CJ1W-EIP21

Lead Free Status / Rohs Status
Lead free / RoHS Compliant
Seven-segment Display
Nomenclature and Functions
Indicator
MS
NS
COMM
100M
10M
Module Status
Network Status Red
Communication Yellow
100 Mbps
10 Mbps
Name
When the power is turned ON (or the Unit is restarted), all of the segments will
flash twice, the IP address set in the EtherNet/IP Unit or built-in EtherNet/IP
port will be displayed on the 7-segment display just once, from right to left.
Afterwards, the rightmost 8 bits of the IP address is displayed in hexadecimal
during normal operation.
Example 1: Displaying IP Address 192.168.250.10
Red
Green
---
Green
---
Yellow
Yellow
Color
The IP address is displayed in decimal, flowing from right to left.
LED status
Lit
Flashing
Lit
Not lit
Lit
Flashing
Lit
Flashing
Not lit
Lit
Not lit
Lit
Not lit
Lit
Not lit
Fatal error
Recoverable error
Normal
Power supply OFF
Fatal error
Recoverable error
Tag data link and message connections established
Tag data link and message connections not established
Offline or power supply OFF
Not transferring data
100BASE-TX link established
100BASE-TX link not established
10BASE-TX link established
10BASE-TX link not established
Transferring data
If the Unit is operating normally, the last digit of the
Unit's IP address is displayed in hexadecimal.
Flashing: The tag data link is stopped.
Lit: The tag data link is operating.
Indicated operating status
Section 2-2
25