Connection Status Codes and Error Processing
01
01
01
01
01
01
01
01
01
General
Connection status
Status
(hex)
011A
011B
0203
0204
0205
0302
0311
0312
0315
Additional
Status
(hex)
Error code returned from origi-
nator:
Connection could not be estab-
lished because the buffer was
full due to high traffic.
Error code returned from target:
The RPI was set to a value that
is below the specifications.
Error code returned from target:
The connection timed out.
Error code returned from target:
The connection-opening pro-
cess timed out.
Error code returned from target:
There was a parameter error in
the frame used to open the con-
nection.
Error occurred at originator or
error code returned from target:
The tag data link’s allowable
bandwidth (pps) was exceeded.
Error code returned from target:
There was a parameter error in
the frame used to open the con-
nection.
Error code returned from target:
There was a parameter error in
the frame used to open the con-
nection.
Error code returned from target:
There was a parameter error in
the frame used to open the con-
nection.
Source of error
An unexpected
network load may
have been
received. Use the
Network Configu-
rator Device Moni-
tor or the Ethernet
Tab Page to check
the bandwidth
usage, and cor-
rect the load. If
there are places
where broadcast
storms occur,
such as loop con-
nections in the
network connec-
tion format, then
correct them.
This error does
not occur.
Tag data link communications from the target timed out. Check
the power supply and cable wiring of the devices in the commu-
nications path, including the target and switches. If performance
has dropped due to heavy load, change the performance set-
tings. For example, increase the timeout time or RPI setting.
There was no response from the target. Check the power supply
and cable wiring of the devices in the communications path,
including the target and switches.
This error does
not occur.
Check the origina-
tor and target con-
nection settings
(number of con-
nections and
RPI).
This error does
not occur.
This error does
not occur.
This error does
not occur.
Configuration 1
An unexpected net-
work load may have
been received. Use
the Network Configu-
rator Device Monitor
or the Ethernet Tab
Page to check the
bandwidth usage,
and correct the load.
If there are places
where broadcast
storms occur, such
as loop connections
in the network con-
nection format, then
correct them.
Depends on the tar-
get’s specifications.
(Contact the target
device’s manufac-
turer.)
Depends on the tar-
get’s specifications.
(Contact the target
device’s manufac-
turer.)
Check the target’s
connection settings
(number of connec-
tions and RPI).
Depends on the tar-
get’s specifications.
(Contact the target
device’s manufac-
turer.)
Depends on the tar-
get’s specifications.
(Contact the target
device’s manufac-
turer.)
Depends on the tar-
get’s specifications.
(Contact the target
device’s manufac-
turer.)
Configuration 2
Handling
Follow the operating
specifications for the
originator. (Consult
the originator manu-
facturer.)
Set the originator’s
RPI setting to 0.5 ms
or greater.
Depends on the orig-
inator’s specifica-
tions. (Contact the
originator device’s
manufacturer.)
Check the originator
and target connec-
tion settings (number
of connections and
RPI).
Depends on the orig-
inator’s specifica-
tions. (Contact the
originator device’s
manufacturer.)
Depends on the orig-
inator’s specifica-
tions. (Contact the
originator device’s
manufacturer.)
Depends on the orig-
inator’s specifica-
tions. (Contact the
originator device’s
manufacturer.)