CJ1W-EIP21 Omron, CJ1W-EIP21 Datasheet - Page 173

no-image

CJ1W-EIP21

Manufacturer Part Number
CJ1W-EIP21
Description
Ethernet I/P Module
Manufacturer
Omron
Datasheet

Specifications of CJ1W-EIP21

Lead Free Status / Rohs Status
Lead free / RoHS Compliant
Setting Tag Data Links
2. When the settings are completed, click the OK Button.
The following table describes the various settings in the dialog box.
Target Device
Connection
Name
Connection I/O
Type
In/Out
Target Variable
Originator Vari-
able
Connection
Type
RPI
Timeout Value
Setting
Selects the target device.
Any name can be given to the connection (up to 32 charac-
ters).
If this field is left blank, a default name will be assigned.
This Connection Name can be used for comments.
When making tag data links in a CS1W-EIP21, CJ1W-EIP21,
CJ2B-EIP21, or CJ2M-EIP21, select Input Only (Tag type).
When making tag data links in other devices, select the con-
nection I/O type specified in that device’s EDS file.
Use the Input Only (ID type) setting when another company’s
node is the originator and does not support connection set-
tings with the Tag type setting.
The connections I/O is automatically displayed based on the
selected connection.
• Input Only: Just In is displayed.
Selects and allocates the target node’s tag set.
• In: Selects the target’s output (produce) tag set.
• Out: Selects the target’s input (consume) tag set.
Selects and allocates the originator node’s tag set.
• In: Selects the originator’s output (produce) tag set.
• Out: Selects the originator’s input (consume) tag set.
Selects whether the data is sent in a multicast or unicast. The
default setting is multicast.
• Multicast connection:
• Point-to-Point connection:
Note Refer to 6-1-2 Overview of Operation for details on
Sets the packet interval (RPI) of each connection between the
originator and target. The interval can be set between 1 and
10,000 ms for the CJ2M-EIP21 and 0.5 and 10,000 ms for
other CPU Units in 0.5-ms units. The default setting is 50 ms
(data refreshed once every 50 ms).
Sets the time until a connection timeout is detected. The time
out value is set as a multiple of the packet interval (RPI) and
can be set to a 4, 8, 16, 32, 64, 128, 256, or 512 multiple. The
default setting is 4× the packet interval (RPI).
Select when the same data is shared by multiple nodes. This
setting is usually selected.
Select when the same data is not being shared by multiple
nodes. In a unicast transmission, other nodes are not bur-
dened with an unnecessary load.
using multicast and unicast transmissions, and counting
the number of connections.
Function
Section 6-2
145

Related parts for CJ1W-EIP21