Error Log Function
14-4 Error Log Function
14-4-1 Error Log Data Specifications
Structure of Each Record
14-4-2 Error Log Registration
Error Log Storage Area
Error Log Overflows
Power Interruptions when
Saving to EEPROM
14-4-3 FINS Commands for Error Logs
364
Errors detected by the EtherNet/IP Unit or built-in EtherNet/IP port are stored
in the error log along with the date and time of their occurrence. The error log
can be read and cleared from the Network Configurator.
Some error log records are cleared when the CPU Unit’s power goes OFF,
and other records are not cleared.
Each error is recorded as one record in the error log.
When an error occurs, information on the error and the time stamp are stored
in the Unit’s internal RAM as an error log record. Serious errors are recorded
in non-volatile EEPROM as well as RAM. The time read from the CPU Unit
during cyclic servicing is used for the time stamp.
The error log records stored in EEPROM are copied to RAM when the Unit
starts operating, so these records are retained even when the Unit’s power is
turned OFF or the Unit is restarted.
When the error log is read, the error log records in RAM are read. When the
error log is cleared, the error log records in both RAM and EEPROM are
erased.
The error log can record up to 64 records. If another error occurs when the log
is full, the oldest record will be erased to make room for the new error record.
If the power supply is interrupted or the Unit is restarted while the error log is
being written to EEPROM, the error log may be corrupted. When the Unit
starts, it performs a checksum test on the error log data read from EEPROM
to detect corrupted data.
The following FINS commands can be sent to the EtherNet/IP Unit or built-in
EtherNet/IP port to read or clear the error log.
For details, refer to Appendix E FINS Commands Addressed to EtherNet/IP
Units or Built-in EtherNet/IP Ports.
Minutes
Day of month
Year
Record length
Number of records
Data type
Bit 15
21
MRC
Command code
Item
02
03
SRC
Detail code
Error code
10 bytes/record
64 records max.
Binary (time information: BCD)
ERROR LOG READ
ERROR LOG CLEAR
Seconds
Hour
Month
Specifications
Bit 00
Function name
Section 14-4