CJ1W-EIP21 Omron, CJ1W-EIP21 Datasheet - Page 387

no-image

CJ1W-EIP21

Manufacturer Part Number
CJ1W-EIP21
Description
Ethernet I/P Module
Manufacturer
Omron
Datasheet

Specifications of CJ1W-EIP21

Lead Free Status / Rohs Status
Lead free / RoHS Compliant
Connection Status Codes and Error Processing
00
01
01
01
01
01
General
Connection status
Status
(hex)
0000
0100
0103
0106
0107
0108
Additional
Status
(hex)
Normal status code:
The connection has been
opened and the tag data link is
communicating normally.
Error code returned from target:
Attempted to open multiple con-
nections at the same connec-
tion.
Error code returned from target:
Attempted to open a connection
with an unsupported transport
class.
Duplicate consumers:
Attempted to open multiple con-
nections for single-consumer
data.
Error code returned from target:
Attempted to close a connec-
tion, but that connection was
already closed.
Error code returned from target:
Attempted to open a connection
with an unsupported connection
type.
Source of error
The following table shows the possible originator/target configurations.
The following table shows the likely causes of the errors causes for each con-
figuration and connection status (code).
Configuration 1
Configuration 2
Configuration 3
Configuration
Email odva@odva.org
WEB www.odva.org
---
This error does
not occur.
This error does
not occur.
If the tag data link
is stopped or
started, this error
may occur accord-
ing to the timing,
but the system will
recover automati-
cally.
This error does
not occur.
This error does
not occur.
Configuration 1
CS1W-EIP21, CJ1W-EIP21,
CJ2H-CPU@@-EIP, CJ2M-
CPU3@
CS1W-EIP21, CJ1W-EIP21,
CJ2H-CPU@@-EIP, CJ2M-
CPU3@
Other company’s device
Originator
---
Depends on the tar-
get’s specifications.
(Contact the target
device’s manufac-
turer for details on
preventing the error
from occurring in the
future.)
Confirm that the tar-
get supports Class
1.
Depends on the tar-
get’s specifications.
(Contact the target
device’s manufac-
turer.)
This error does not
occur.
Check which con-
nection types can be
used by the target.
(Contact the manu-
facturer.)
Only multicast and
point-to-point can be
set.
Configuration 2
Handling
CS1W-EIP21, CJ1W-EIP21,
CJ2H-CPU@@-EIP, CJ2M-
CPU3@
Other company’s device
CS1W-EIP21, CJ1W-EIP21,
CJ2H-CPU@@-EIP, CJ2M-
CPU3@
---
Depends on the orig-
inator’s specifica-
tions.
(Contact the origina-
tor device’s manufac-
turer for details on
preventing the error
from occurring in the
future.)
Confirm that the
originator supports
Class 1.
If the tag data link is
stopped or started,
this error may occur
according to the tim-
ing, but the system
will recover automat-
ically.
This is not an error
because the connec-
tion is already
closed.
Check which con-
nection types can be
used by the origina-
tor.
(An error will occur if
a connection other
than multicast or
point-to-point is set.)
Configuration 3
Target
Section 14-3
359

Related parts for CJ1W-EIP21