Routing Tables
8-4-2
208
PLC #1 (local node)
Connecting and Using a Peripheral Device for the PLC
PLC #1
relay network table
To go to network #3,
first go to node #3 at
network #1.
End
network
2
3
Relay
network
Note
1
1
Note
Node #1
Relay
node
Network #1
3
3
The following example shows routing tables for sending data from PLC #1 (the
local node: network address 1, node address 1) to PLC #4 (the destination
node: network address 3, node address 2).
In the above example, the routing tables required for a message to reach PLC
#4 from PLC #1 are shown. Additional settings would be required in the rout-
ing tables for a message to reach PLC #1 from PLC #4. Refer to 8-4-3 Rout-
ing Table Setting Examples for routing table setting examples.
Routing tables must be created by a CX-Integrator connected to the PLC.
(They cannot be created using a Programming Console.) For details on how
to connect and use the CX-Integrator, refer to the CX-Integrator Operation
Manual (W445). (CX-Integrator is automatically installed when CX-One is
installed.)
1. When routing tables are transferred from the CX-Integrator to the PLC, all
2. To transfer routing tables for multiple nodes to a PLC in one batch, connect
3. Routing tables can only be transferred as a batch to multiple nodes within
PLC #2 (relay node)
End
network
To go to network #3,
first go to node #2 at
network #2.
PLC #2
relay network table
of the CPU Bus Unit are reset so that the routing tables that have been cre-
ated can be read and enabled. Before transferring the routing tables, con-
firm that there will be no problems in the system when the CPU Bus Units
are reset.
the CX-Integrator to a PLC with only one Communications Unit mounted.
Routing tables cannot be transferred to other nodes from a PLC with mul-
tiple Communications Units mounted.
the same network as the PLC to which the CX-Integrator is connected.
Node #2
3
Relay
network
2
Relay
node
Network #2
2
Node #1
Node #3
PLC #3
(relay node)
(To go to network #3
according to the local
network table, go
through unit
number 1 of the local
CPU Rack.)
PLC #3
local network table
Local
network
address
2
3
Network #3
Node #2
Unit #0
Node #1
Unit #1
Unit
number
0
1
End network
(The network is the same,
so go to node #2 at network #3.)
PLC #4 (destination node)
Node #2
Section 8-4