WRITE WORD DATA
106
Explicit Message Communications
Instance ID (command)
Specify the data area containing the desired data in 1 byte (2-digit hexadeci-
mal). Use one of the codes listed in the following table.
Address L and Address H (command)
Specify the starting word address of the read data in hexadecimal as follows:
Number of words (command)
Specify the number of words of data to read in 1 byte (2-digit hexadecimal).
The allowed range is 01 to 64 (Hex), which is equivalent to 1 to 100 decimal.
Number of bytes received (response)
Indicates the number of bytes of data (in hexadecimal) from the “source node
number.”
Source node number (response)
Indicates the node number (in hexadecimal) of the CPM2B-S that returned
the response.
Read data (response)
Contains the desired data read from the specified data area. Word data is
returned with the leftmost byte (bits 8 to 15) preceding the rightmost byte (bits
0 to 7).
Precautions
The range of data specified by the data area (instance ID), starting address
(Address L and Address H), and number of words parameters must not
exceed the range of the CPM2B-S data area.
Writes data from the DeviceNet Master to the specified node’s data area in
word-units (two-byte units). When word data is being written, the leftmost byte
is written before the rightmost byte. Up to 100 words can be written at one
time.
Command Format
01 (Hex)
02 (Hex)
03 (Hex)
04 (Hex)
05 (Hex)
06 (Hex)
07 (Hex)
Destination node number
Code
Address L: The rightmost two digits of the 4-digit starting address.
Address H: The leftmost two digits of the 4-digit starting address.
Service code
IR area
IR area
DM area
LR area
HR area
AR area
Timer/Counter area
Class ID
Area name
Instance ID
Address L
Address H
Leftmost
byte
IR 000 to IR 049
IR 200 to IR 227
DM 0000 to DM 2047
LR 00 to LR 15
HR 00 to HR 19
AR 00 to AR 23 (read area only)
TC 000 to TC 255
Rightmost byte
(200 bytes max.)
Address range
Write data
Leftmost byte
Section 7-3
Rightmost byte