XW2Z-070T-1 Omron, XW2Z-070T-1 Datasheet - Page 89

no-image

XW2Z-070T-1

Manufacturer Part Number
XW2Z-070T-1
Description
Special Nissan
Manufacturer
Omron
Series
XW2Zr
Type
DB09r
Datasheet

Specifications of XW2Z-070T-1

1st Connector
Plug, Male Pins
2nd Connector
Plug, Male Pins
Number Of Positions
9
Length
2.3' (701.0mm)
Color
Beige, Individual (Round)
Usage
Communication
Contact Finish
Gold
Contact Finish Thickness
15µin (0.38µm)
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
Shielding
-
Lead Free Status / Rohs Status
Lead free / RoHS Compliant
Other names
XW2Z070T1
PC Setup
RS-232C Port Communications Settings
The following settings are read regularly by the CPU while the PC is ON.
If pin 3 of the CPM2B-S CPU Unit’s DIP switch is ON, communications through the CPM2B-S’ RS-232C port are gov-
erned by the default settings (all 0) regardless of the settings in DM 6645 through DM 6649.
DM 6645
DM 6646
DM 6647
DM 6648
DM 6649
Word(s)
00 to 03
04 to 07
08 to 11
12 to 15
00 to 07
08 to 15
00 to 15
00 to 07
08 to 11
12 to 15
00 to 07
08 to 15
Bit(s)
Port settings
0 (Hex): Standard (1 start bit, 7 data bits, even parity, 2 stop bits, 9,600 bps),
1 (Hex): Settings in DM 6646
(Any other setting will cause a non-fatal error and AR 1302 will turn ON.)
CTS control setting
0 (Hex): Disable CTS control; 1 (Hex): Enable CTS control
(Any other setting will cause a non-fatal error and AR 1302 will turn ON.)
Link words for 1:1 data link
0 (Hex): LR 00 to LR 15 (Any other settings are ineffective.)
Communications mode
0 (Hex): Host Link; 1 (Hex): No-protocol; 2 (Hex): 1:1 PC Link Slave;
3 (Hex): 1:1 PC Link Master; 4 (Hex): NT Link
(Any other setting causes a non-fatal error and turns ON AR 1302.)
Baud rate
00 (Hex): 1,200 bps; 01 (Hex): 2,400 bps; 02 (Hex): 4,800 bps;
03 (Hex): 9,600 bps; 04 (Hex): 19,200 bps
Frame format
00 (Hex):
01 (Hex):
02 (Hex):
03 (Hex):
04 (Hex):
05 (Hex):
06 (Hex):
07 (Hex):
08 (Hex):
09 (Hex):
10 (Hex):
11 (Hex):
(Any other setting specifies standard settings (1 start bit, 7 data bits; even parity, 2 stop bits,
9,600 bps), causes a non-fatal error, and turns ON AR 1302.)
Transmission delay (0000 to 9999 BCD sets a delay of 0 to 99,990 ms.)
(Any other setting specifies a delay of 0 ms, causes a non-fatal error, and turns ON AR 1302.)
Node number (Host Link)
00 to 31 (BCD)
(Any other setting specifies a node number of 00, causes a non-fatal error, and turns ON AR
1302.)
Start code selection for no-protocol communications
0 (Hex): Disables start code; 1 (Hex): Enables start code in DM 6649
(Any other setting disables the start code, causes a non-fatal error, and turns ON AR 1302.)
End code selection for no-protocol communications
0 (Hex): Disables end code; 1 (Hex): Enables end code in DM 6649;
2 (Hex): Sets end code of CR, LF.
(Any other setting disables the end code, causes a non-fatal error, and turns ON AR 1302.)
Start code (00 to FF)
(This setting is valid only when bits 8 to 11 of DM 6648 are set to 1.)
When bits 12 to 15 of DM 6648 set to 0:
Sets the number of bytes to receive. (00: 256 bytes; 01 to FF: 1 to 255 bytes)
When bits 12 to 15 of DM 6648 set to 1:
Sets the end code. (00 to FF)
Host Link unit number: 0
Start bits
1 bit
1 bit
1 bit
1 bit
1 bit
1 bit
1 bit
1 bit
1 bit
1 bit
1 bit
1 bit
Data bits
7 bits
7 bits
7 bits
7 bits
7 bits
7 bits
8 bits
8 bits
8 bits
8 bits
8 bits
8 bits
Function
Stop bits
1 bit
1 bit
1 bit
2 bits
2 bits
2 bits
1 bit
1 bit
1 bit
2 bits
2 bits
2 bits
Parity
Even
Odd
None
Even
Odd
None
Even
Odd
None
Even
Odd
None
Section 4-6
77

Related parts for XW2Z-070T-1