XW2Z-070T-1 Omron, XW2Z-070T-1 Datasheet - Page 42

no-image

XW2Z-070T-1

Manufacturer Part Number
XW2Z-070T-1
Description
Special Nissan
Manufacturer
Omron
Series
XW2Zr
Type
DB09r
Datasheet

Specifications of XW2Z-070T-1

1st Connector
Plug, Male Pins
2nd Connector
Plug, Male Pins
Number Of Positions
9
Length
2.3' (701.0mm)
Color
Beige, Individual (Round)
Usage
Communication
Contact Finish
Gold
Contact Finish Thickness
15µin (0.38µm)
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
Shielding
-
Lead Free Status / Rohs Status
Lead free / RoHS Compliant
Other names
XW2Z070T1
Board Components and their Functions
6. DeviceNet Indicators
7. Input Indicators
The following indicators show the status DeviceNet communications.
The input indicators are lit when the corresponding input terminal is ON.
The status of an input indicator will reflect the status of the input even when
that input is being used for a high-speed counter.
Note a) When interrupt inputs are used in interrupt input mode, the indica-
PERI
(yellow)
RD
(yellow)
SD
(yellow)
ERC
(red)
MS
NS
Indicator
Indicator
b) Input indicators will reflect the status of the corresponding inputs
tor may not light even when the interrupt condition is met if the in-
put is not ON long enough. When a high-speed counter is being
used, the indicator may not light depending on the speed of the
pulses.
even when the PC is stopped, but the corresponding input bits will
not be refreshed.
Green
Red
---
Green
Red
---
ON
OFF
Flashing Data is being received via CompoBus/S.
OFF
Flashing Data is being transmitted via CompoBus/S.
OFF
Flashing A CompoBus/S communications error occurred.
OFF
Color
Status
ON
Flashing Incomplete settings (reading switch settings)
ON
Flashing Non-fatal error such as incorrect switch settings
OFF
ON
Flashing Online/Communications not established
ON
Flashing Non-fatal communications error
OFF
Status
Data is being transferred via the peripheral port.
The peripheral port is not being used.
Data isn’t being received via CompoBus/S.
Data isn’t being transmitted via CompoBus/S.
A CompoBus/S communications error hasn’t occurred.
Normal status
Fatal hardware error (watchdog timer error)
• Power is not being supplied.
• Waiting for initialization to start
• Reset in progress
Online/Communications established
(Normal network status when communications
have been established)
(Normal network status when communications
haven’t been established)
Fatal communications error (The Unit detected
an error indicating that network communications
are disabled.)
• Node number duplication
• Bus off error detected
(Communications timeout)
Offline/Power supply OFF
Waiting for completion of the node number dupli-
cation check in the Master.
• Incorrect switch settings
• Power supply OFF
Meaning
Meaning
Section 2-2
29

Related parts for XW2Z-070T-1