Self-diagnostic Functions
Power interruption
(no message)
MEMORY ERR
NO END INST
I/O BUS ERR
I/O UNIT OVER
SYS FAIL FALS**
(** is 01 to 99 or 9F.)
1.
Message
Fatal Errors
00
F1
F0
C0
E1
01 to 99 A FALS(07) instruction has been executed in the program. Check the FALS number to
9F
FALS
No.
Power has been interrupted for more than 2 ms.
Check power supply voltage and power lines. Try to power-up again.
AR 1308 ON: There is a non-existent bit or word address in the user program. Check the
program and correct errors.
AR 1309 ON: An error has occurred in flash memory. Replace the CPU Board.
AR 1310 ON: A checksum error has occurred in read-only DM (DM 6144 to DM 6599).
Check and correct the settings in the read-only DM area.
AR 1311 ON: A checksum error has occurred in the PC Setup. Initialize the PC Setup
and input the settings again.
AR 1312 ON: A checksum error has occurred in the program. Check the program and
correct any errors detected.
AR 1313 ON: A checksum error has occurred in the expansion instructions data and all
function codes have been set the their default values. Reset the expansion instructions.
AR 1314 ON: Data was not maintained in an area specified for holding. Clear the error,
check the data in the areas specified for holding, and try again.
END(01) is not written in the program. Write END(01) at the end of the program.
An error has occurred during data transfer between the CPU Board and an Expansion I/
O Board. Check the Board’s connecting cable.
Too many Expansion I/O Boards have been connected. Check the Board configuration.
determine the conditions that caused execution, correct the cause, and clear the error.
The cycle time has exceeded the Maximum (Watch) Cycle Time setting (DM 6618).
Check the cycle time and adjust the Maximum Cycle Time setting if necessary.
PC operation and program execution will stop and all outputs from the PC will
be turned OFF when any of these errors have occurred. CPM2B-S operation
can’t be restarted until the PC is turned off and then on again or a Program-
ming Device is used to switch the PC to PROGRAM mode and clear the fatal
error.
All CPU Board indicators will be OFF for the power interruption error. For all
other fatal operating errors, the POWER and ERR indicators will be lit. The
RUN indicator will be OFF.
Meaning and appropriate response
Section 9-3