XW2Z-070T-1 Omron, XW2Z-070T-1 Datasheet - Page 119

no-image

XW2Z-070T-1

Manufacturer Part Number
XW2Z-070T-1
Description
Special Nissan
Manufacturer
Omron
Series
XW2Zr
Type
DB09r
Datasheet

Specifications of XW2Z-070T-1

1st Connector
Plug, Male Pins
2nd Connector
Plug, Male Pins
Number Of Positions
9
Length
2.3' (701.0mm)
Color
Beige, Individual (Round)
Usage
Communication
Contact Finish
Gold
Contact Finish Thickness
15µin (0.38µm)
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
Shielding
-
Lead Free Status / Rohs Status
Lead free / RoHS Compliant
Other names
XW2Z070T1
Explicit Message Communications
Response Format
Parameters
Destination node number (command)
Specify the node number of the CPM2B-S where the data will be written.
Specify the node number in 1 byte (2-digit hexadecimal).
Service code (command, response)
Specify 1F (Hex) in the command.
The leftmost bit of the service code is turned ON in the response, so 9F (Hex)
is returned.
Class ID (command)
Always 2F (Hex).
Instance ID (command)
Specify the data area where data will be written. Specify one of the codes
listed in the following table in 1 byte (2-digit hexadecimal).
Address L and Address H (command)
Specify the starting word address where data will be written. Specify the
address in hexadecimal as follows:
Write data (command)
Contains the data that will be written in the specified data area. Input word
data with the leftmost byte (bits 8 to 15) preceding the rightmost byte (bits 0 to
7).
Number of bytes received (response)
Indicates the number of bytes of data (in hexadecimal) from the “source node
number” on.
Source node number (response)
Indicates the node number (in hexadecimal) of the CPM2B-S that returned
the response.
Precautions
The range of data specified by the data area (instance ID), starting address
(Address L and Address H), and write data parameters must not exceed the
range of the CPM2B-S data area.
01 (Hex)
02 (Hex)
03 (Hex)
04 (Hex)
05 (Hex)
07 (Hex)
Code
Address L: The rightmost two digits of the 4-digit starting address.
Address H: The leftmost two digits of the 4-digit starting address.
IR area
IR area
DM area
LR area
HR area
Timer/Counter area
Area name
Number of bytes received
Source node number
Service code
IR 000 to IR 049
IR 200 to IR 227
DM 0000 to DM 2047
LR 00 to LR 15
HR 00 to HR 19
TC 000 to TC 255
Address range