FX1S-30MR-ES/UL MITSUBISHI, FX1S-30MR-ES/UL Datasheet - Page 217

PLC, 16 IN, 14 RELAY OUT, 110V/2

FX1S-30MR-ES/UL

Manufacturer Part Number
FX1S-30MR-ES/UL
Description
PLC, 16 IN, 14 RELAY OUT, 110V/2
Manufacturer
MITSUBISHI
Datasheet

Specifications of FX1S-30MR-ES/UL

No. Of Analogue Inputs
16
No. Of Analogue Outputs
14
Ip/nema Rating
IP10
Approval Bodies
CE, CUL, UL
External Depth
49mm
External Length / Height
90mm
External Width
60mm
Mounting Type
Panel
5.9.1
FX Series Programmable Controlers
RS (FNC 80)
Points to note:
a) This instruction has many automatically
b) The RS instruction has two parts, send
c) Data cannot be sent while a message is
d) More than one RS instruction can be
e) Refer to the FX Communications Manual
RS
FNC 80
(Serial Com-
munications
instruction)
Mnemonic
when using this function
defined devices. These are listed in the
boxed column to the right of this page.
(or transmission) and receive. The first
elements of the RS instruction specify the
transmission data buffer (S) as a head
address, which contains m number of
elements in a sequential stack.
The specification of the receive data area
is contained in the last two parameters of
the RS instruction. The destination (D)
for received messages has a buffer or
stack length of n data elements. The size
of the send and receive buffers dictates
how large a single message can be.
Buffer sizes may be updated at the
following times:
1) Transmit buffer - before transmission
occurs, i.e. before M8122 is set ON
2) Receive buffer - after a message has
been received and before M8123 is
reset.
being received, the transmission will be
delayed - see M8121.
programmed but only one may be active
at any one time.
Used to control
serial
communications
from/to the
programmable
controller
Function
D
(including
file
registers)
S
K, H,
D
m = 1 to
256, FX2N
1 to 4096.
Operation:
This instruction performs the direct control of
communications over FX and FX
adapters which connect to the left hand port of the
Main Processing Unit, i.e. FX
232ADP etc.
m
Operands
Data devices:
D8120 - Contains the configuration parameters for
D8122 - Contains the current count of the number of
D8123 - Contains the current count of the number of
D8124 - Contains the ASCII code of the character used
D8125 - Contains the ASCII code of the character used
Operational flags:
M8121 - This flag is ON to indicate a transmission is
M8122 - This flag is used to trigger the transmission of
M8123 - This flag is used to identify (when ON) that a
M8124 - Carrier detect flag. This flag is for use with FX
M8161 - 8 or 16 bit operation mode ON = 8 bit mode
D
communication, i.e. Baud rate,Stop bits etc. Full
details over the page
remaining bytes to be sent in the currently
transmitting message.
received bytes in the ‘incoming’ message.
to signify a message header - default is ‘STX’,
02 HEX.
to signify a message terminator -default is
‘ETX’, 03 HEX.
b e i n g d e l a y e d u n t i l t h e c u r r e n t r e c e iv e
operation is completed.
data when it is set ON.
complete message has been received.
and FX2C Main Processing Units. It is typically
useful in modem communications
where only the lower 8 bits in each source or
destination device are used, i.e. only one ASCII
character is stored in one data register OFF =
16bit mode where all of the available source/
destination register is used, i.e. two ASCII
characters are stored in each data register.
D
Assigned devices
K, H,
D
m = 1 to
256, FX2N
1 to 4096
n
Applied Instructions 5
0N
0N
RS: 9 steps
Program steps
communication
-232ADP, FX-
5-95