FX1S-30MR-ES/UL MITSUBISHI, FX1S-30MR-ES/UL Datasheet - Page 287

PLC, 16 IN, 14 RELAY OUT, 110V/2

FX1S-30MR-ES/UL

Manufacturer Part Number
FX1S-30MR-ES/UL
Description
PLC, 16 IN, 14 RELAY OUT, 110V/2
Manufacturer
MITSUBISHI
Datasheet

Specifications of FX1S-30MR-ES/UL

No. Of Analogue Inputs
16
No. Of Analogue Outputs
14
Ip/nema Rating
IP10
Approval Bodies
CE, CUL, UL
External Depth
49mm
External Length / Height
90mm
External Width
60mm
Mounting Type
Panel
6.8
FX Series Programmable Controller
Link and Special Operation
Devices (M8070 to M8099 and D8070 to D8099)
For symbol key see page 6-1.
M8070 ( R)
M8071 ( R)
M8072 ( )
M8073 ( )
M8075 -M8098 Reserved
M8099 ( )
Diagnostic
Note 3:
Note 4:
General note:
Device
• If the unit or block corresponding to a programmed
• An I/O bus check is executed when M8069 is
• HPP refers to Handy programming panel.
I / O number is not actually loaded, M8060 is set to
ON and the first device number of the erroneous
block is written to D8060.
turned ON. If an error occurs, error code 6103 or
6104 is written to D8069 and M8061 is turned ON.
Driven when the PLC is a
master station in a parallel
link application
Driven when the PLC is a
slave station in a parallel
link application
ON while the PLC is operat-
ing in a parallel link
ON when M8070/ M8071
are incorrectly set during
parallel link operations
High speed free timer oper-
ation
Operation
D8070 ( )
D8071 - D8098 Reserved
D8099
Diagnostic
Device
Parallel link watchdog time -
500 msec
Free ring timer, range: 0 to
32,767 in units of 0.1 msec
(for use in measuring input
pulse durations)
Operation
Diagnostic Devices 6
6-9