Specifications of FX1S-30MR-ES/UL

No. Of Analogue Inputs
16
No. Of Analogue Outputs
14
Ip/nema Rating
IP10
Approval Bodies
CE, CUL, UL
External Depth
49mm
External Length / Height
90mm
External Width
60mm
Mounting Type
Panel
FX Series Programmable Controllers
Points Of Technique 10
In this example these three modes are
selected by an external rotary switch. The
rotary switch is not connected to the PLC but
to the I/O bus on the rear of the DU unit.
The use of the rotary switch means that the
selected modes are mutually exclusive in
their operation. For an operator friendly
environment the currently selected mode is
displayed on the DU screen (again this could
be by use of the DUs ASCII function).
The start/ stop controls are touch keys on the
DU screen. When a mode is selected the
input received at the DU unit momentarily
activates one of the following auxiliary relays:
Rotary switch:
position 1 ’Step’ - Step operation: DU input I0,
controls bit device M32 position 2 ’Cycle’ -
Single cycle operation:
DU input I1, controls bit device M33 position 3
’Auto’ - Automatic operation: DU input I2,
controls bit device M34
Key assignment for DU screen above:
Start = M36
Stop = M37
The program run in all three mode choices is
shown opposite. As noted earlier, the ’Step’
mode will require an operator to press the
’Start’ key to start each new STL block. This
could be viewed as an additional transfer
condition between each state. However, the
user is not required to program this as the IST
i n s t r u c t i o n c o n t r o l s t h i s o p e r a t i o n
automatically.
The ’Cycle’ mode will process the program
from STL step S2, all the way through until
STL step S2 is encountered again. Once
more the IST instruction ensures that only
one cycle is com pleted for each initial
activation of the ’Start’ input.
Finally as suggested by the name, ’Auto’
mode will continuously cycle through the
program until the ’Stop’ button is pressed.
The actual halting of the program cycling will
occur when the currently active cycle is
completed.
10-12

Related parts for FX1S-30MR-ES/UL