FX1S-30MR-ES/UL MITSUBISHI, FX1S-30MR-ES/UL Datasheet - Page 293

PLC, 16 IN, 14 RELAY OUT, 110V/2

FX1S-30MR-ES/UL

Manufacturer Part Number
FX1S-30MR-ES/UL
Description
PLC, 16 IN, 14 RELAY OUT, 110V/2
Manufacturer
MITSUBISHI
Datasheet

Specifications of FX1S-30MR-ES/UL

No. Of Analogue Inputs
16
No. Of Analogue Outputs
14
Ip/nema Rating
IP10
Approval Bodies
CE, CUL, UL
External Depth
49mm
External Length / Height
90mm
External Width
60mm
Mounting Type
Panel
6.16
FX Series Programmable Controller
Error Code Tables
D8061
PLC Hardware
error
D8062
PC/HPP
communication
error
D8063
Serial
communication
errors
Error Detection
Error Detection
Error Detection
Device
Device
Device
Stored Error
Stored Error
Stored Error
Number
Number
Number
0000
6101
6102
6103
6104
6105
0000
6201
6202
6203
6204
6205
0000
6301
6302
6303
6304
6305
6306
6312
6313
6314
RAM error
Operation circuit error
I/O bus error (M8069 = ON)
Extension unit 24V failure (M8069=ON)
Watch Dog Timer error
No error
Parity/ overrun/ framing error
Communications character error
Communication data sum check error
Data format error
Command error
No error
Parity/ overrun/ framing error
Comms character error
Comms data sum check error
Comms data format error
Command error
485 Network - received command other
than GW (global) when station number
was FF
Watchdog timer error
Parallel link character error
Parallel link data sum check error
Parallel link data format error
No error
Associated Meaning
Associated Meaning
Associated Meaning
Check the cable connec-
tion between the pro-
gramming device and
the PLC
Program execution time
has exceeded the WDT
time value set in D8000.
Check the cable connec-
tion between the pro-
gramming device and
the PLC
Check both power and
communications con-
nections
Special note regarding
the 485 network:
Because these errors
are not transmitted
through the network,
they must be monitored
by the unit acting as
Master to the network
Diagnostic Devices 6
Action
Action
Note
6-15

Related parts for FX1S-30MR-ES/UL