FX1S-30MR-ES/UL MITSUBISHI, FX1S-30MR-ES/UL Datasheet - Page 297

PLC, 16 IN, 14 RELAY OUT, 110V/2

FX1S-30MR-ES/UL

Manufacturer Part Number
FX1S-30MR-ES/UL
Description
PLC, 16 IN, 14 RELAY OUT, 110V/2
Manufacturer
MITSUBISHI
Datasheet

Specifications of FX1S-30MR-ES/UL

No. Of Analogue Inputs
16
No. Of Analogue Outputs
14
Ip/nema Rating
IP10
Approval Bodies
CE, CUL, UL
External Depth
49mm
External Length / Height
90mm
External Width
60mm
Mounting Type
Panel
FX Series Programmable Controller
Error Detection
D8067
Operation
error
D8067
PID
Operation
error
Device
Stored Error
Number
0000
6701
6702
6703
6704
6705
6706
6707
6708
6709
6730
6732
6733
6734
6735
6736
6740
6742
6743
6744
6745
6746
6747
6750
6751
6752
No error
1) No jump destination for CJ or CALL
2) A label is designated in a block that
3) An independent label is designated in
6 or more CALL instructions have been
nested together
3 or more interrupts have been nested
together
6 or more FOR - NEXT loops have been
nested together
An incompatible device has been speci-
fied as an operand for an applied instruc-
tion
A device has been specified outside of
the allowable range for an applied instruc-
tion operand
A file register has been accessed which is
outside of the users specified range
FROM/ TO instruction error
Other error, i.e. missing IRE/ SRET, unau-
thorized FOR - NEXT relationship
Sampling time T
Input filter value
Proportional gain K
Integral time constant T
Derivative gain K
Derivative time constant T
(T
Sampling time TS is less than the pro-
gram scan time.
Current value
Calculated error exceeds its limits
Integral result exceeds its limits
Derivative gain over, or differential value
exceeds allowable range
Derivative result exceeds its limits
Total PID result exceeds its limits
SV - PV
(SV - PV
Large Overshoot of the Set Value
Large fluctuations during Autotuning Set
Process
D
instructions
comes after the END instruction
a FOR-NEXT loop or a subroutine
<0 or >32767)
nf
nf
Associated Meaning
< 150, or system is unstable
has wide, fast variations)
exceeds its limits
S
D
(T
( <0 or >=101)
(K
P
S
(K
D
<0 or >32767)
<0 or >=101)
P
I
<0 or >32767)
(T
D
I
<0 or >32767)
These error occur during
the execution of an oper-
ation.
When an operation error
occurs, STOP the PLC
enter programming ode
and correct the fault.
Note: operation errors
can occur even when the
syntax or circuit design
is correct, e.g.
D500Z is a valid state-
ment within an FX PLC.
But if Z had a value of
100, the data register
D600 would be
attempted to be
accessed. This will
cause an operation error
as there is no D600
device available.
The identified parameter
is specified outside of its
allowable range
Execution ceases PID
instruction must be reset
before execution will
resume
TS is set to program
scan time -
Execution will continue.
Data affected resets to
the nearest limit value.
For all errors except
6745, this will either be a
minimum of -32768 or a
maximum of +32767.
Execution will continue.,
but user should reset
PID instruction.
The error fluctuation is
outside the normal oper-
ation limits for the PID
instruction. Execution
ceases. PID instruction
must be reset.
Diagnostic Devices 6
Action
6-19

Related parts for FX1S-30MR-ES/UL