FX1S-30MR-ES/UL MITSUBISHI, FX1S-30MR-ES/UL Datasheet - Page 281

PLC, 16 IN, 14 RELAY OUT, 110V/2

FX1S-30MR-ES/UL

Manufacturer Part Number
FX1S-30MR-ES/UL
Description
PLC, 16 IN, 14 RELAY OUT, 110V/2
Manufacturer
MITSUBISHI
Datasheet

Specifications of FX1S-30MR-ES/UL

No. Of Analogue Inputs
16
No. Of Analogue Outputs
14
Ip/nema Rating
IP10
Approval Bodies
CE, CUL, UL
External Depth
49mm
External Length / Height
90mm
External Width
60mm
Mounting Type
Panel
6.2
FX Series Programmable Controller
Clock Devices (M8010 to M8019 and
D8010 to D8019)
For symbol key see page 6-1.
M8010
M8011 ( )
10 msec
clock pulse
M8012 ( )
100 msec
clock pulse
M8013 ( )
1 sec
clock pulse
M8014 ( )
1 min
clock pulse
M8015
Time setting
M8016
Register data
M8017
Min. rounding
M8018 ( )
RTC available
M8019
Setting error
The following devices apply to FX
Diagnostic
Device
Reserved
Oscillates in 10 msec cycles
Oscillates in 100 msec
cycles
Oscillates in 1 sec cycles
Oscillates in 1 min cycles
When ON - clock stops, ON
When ON D8013 to 19 are
frozen but clock continues
When pulsed ON set RTC
to nearest minute
When ON Real Time Clock
is installed
Clock data has been set out
of range
OFF restarts clock
Operation
a real time clock option board installed.
2N,
FX
1N
and FX
D8010 ( )
Present scan
time
D8011 ( )
Minimum
scan time
D8012 ( )
Maximum
scan time
D8013
Seconds
D8014
Minute data
D8015
Hour data
D8016
Day data
D8017
Month data
D8018
Year data
D8019
Weekday data
Diagnostic
Device
1S
PLC’s and to the FX
Current operation cycle / scan
time in units of 0.1 msec
Minimum cycle/ scan time in
units of 0.1 msec
Maximum cycle/ scan time in
units of 0.1 msec
(waiting time for constant scan
mode is not included)
Seconds data for use with
an RTC cassette (0 - 59)
(FX
Minute data for use with an
RTC cassette (0-59)
Hour data for use with an RTC
cassette (0-23)
Day data for use with an RTC
cassette (1-31)
Month data for use with an
RTC cassette (1-12)
Year data for use with an RTC
cassette (0-99)
Weekday data for use with an
RTC cassette (0-6)
0(S)
, FX
Operation
Diagnostic Devices 6
0N
2NC
see note 2)
6-3
PLC when

Related parts for FX1S-30MR-ES/UL