FX1S-30MR-ES/UL MITSUBISHI, FX1S-30MR-ES/UL Datasheet - Page 264

PLC, 16 IN, 14 RELAY OUT, 110V/2

FX1S-30MR-ES/UL

Manufacturer Part Number
FX1S-30MR-ES/UL
Description
PLC, 16 IN, 14 RELAY OUT, 110V/2
Manufacturer
MITSUBISHI
Datasheet

Specifications of FX1S-30MR-ES/UL

No. Of Analogue Inputs
16
No. Of Analogue Outputs
14
Ip/nema Rating
IP10
Approval Bodies
CE, CUL, UL
External Depth
49mm
External Length / Height
90mm
External Width
60mm
Mounting Type
Panel
5.14.6
FX Series Programmable Controlers
TWR (FNC 167)
The seven devices
Points to note:
This instruction removes the need to use M8015 during real time clock setting. When setting
the time it is a good idea to set the source data to a time a number of minutes ahead and then
drive the instruction when the real time reaches this value.
TWR
FNC 167
(Time
Write)
Mnemonic
Device
S
S
S
S
S
S
S
+0
+1
+2
+3
+4
+5
+6
Sets the real time
clock to the value
stored in a group
of registers
Meaning
Seconds
Function
Minutes
Month
Hours
Date
Year
Day
0-6 (Sun-Sat)
T, C, D
Note: 7 consecutive devices are used.
Values
00-99
01-12
01-31
00-23
00-59
00-59
Contents:
The 7 data devices specified with the head
address S are used to set a new current value of
the real time clock.
Operands
S
Device
D8018
D8017
D8016
D8015
D8014
D8013
D8019
Meaning
Seconds
Minutes
Month
Hours
Date
Year
Day
Applied Instructions 5
TWR, TWRP:
5 steps
Program steps
5-142