FX1S-30MR-ES/UL MITSUBISHI, FX1S-30MR-ES/UL Datasheet - Page 335

PLC, 16 IN, 14 RELAY OUT, 110V/2

FX1S-30MR-ES/UL

Manufacturer Part Number
FX1S-30MR-ES/UL
Description
PLC, 16 IN, 14 RELAY OUT, 110V/2
Manufacturer
MITSUBISHI
Datasheet

Specifications of FX1S-30MR-ES/UL

No. Of Analogue Inputs
16
No. Of Analogue Outputs
14
Ip/nema Rating
IP10
Approval Bodies
CE, CUL, UL
External Depth
49mm
External Length / Height
90mm
External Width
60mm
Mounting Type
Panel
10.3.2
FX Series Programmable Controllers
Remote RUN/STOP control
The FX family of programmable controllers can be controlled, i.e. switched into RUN or STOP
modes and have devices monitored by use of intelligent external control devices.
These includes such items as computers, the Mitsubishi FX data access units and Graphic
Operator Terminals.
The following example utilizes a graphic FX-DU unit:
Explanation:
The programmable controller needs no special wiring
or additional programming for this example.
The only condition required is that the PLC would not
normally be in a RUN state, i.e., there is no connection
to the RUN terminal and the RUN/STOP switch on
PLC’s that have one is set in the STOP position.
The DU should be programmed with 'SWITCH'
devices driving the three special M codes M8035,36
and 37. By activating the 'SWITCH' devices for M8035
and M8036 the PLC can be switched into a RUN state,
while driving the 'SWITCH' device M8037 will put the
PLC into a STOP state.
Example 'SWITCH' device setting opposite.
Use an 'Alternate' switch for M8035 and M8036 and use a 'Momentary' switch for M8037.
(see DU operation manual for SWITCH operation and programming)
Note: While M8035 and M8036 are ON the MPU can not be changed to STOP mode using the
RUN terminal or RUN/STOP switch. Either set M8037 ON, or reset M8035 and M8036, to
return to the normal operating state.
Range of Mitsubishi graphic FX-DU units:
FX-25DU-E - a 4 line text/graphic unit.
FX-30DU-E - a 4 line text/graphics display unit with membrane style keypad.
FX-40DU-TK-E - a 7 line, touch key, text/graphics display unit with numeric keypad.
FX-50DU-TK(S)-E - a 15 line, touch screen, color text/graphics display unit.
F930GOT-BWD - a 5 line, touch screen, monochrome text/graphics advanced display unit.
F940GOT-SWD/LWD-E - a 15 line, touch screen, color text/graphics advanced display unit.
FX
With FX
position, it is still possible to do a remote STOP by forcing M8037 ON.
Return to RUN by resetting M8037.
1N
, FX
1N,
2N
FX
and FX
2N
and FX
2NC
Remote STOP
2NC
units, even if the RUN terminal or RUN/STOP switch is in the RUN
1. Remote Mode
2. Remote Start
3. Remote Stop
Points Of Technique 10
POW ER
10-3
SWITCH for...
M8035
M8036
M8037

Related parts for FX1S-30MR-ES/UL