Firmware Update Utilities—MPCBL0050
10.7.3
Note:
10.7.4
September 2007
Order Number: 318146-001
To read the threshold from a device via RMCP bridge, specify the threshold mode (
threshold
The syntax of the command is:
# sbcupdate -I lan -H <ip address of shelf manager> -U <username>
For example, users would execute the following command:
# sbcupdate -I lan -H 10.90.90.91 -U root -P cmmrootpass -t 0x8e
Changing Thresholds Values Using KCS Interface
To change the threshold values using the KCS interface, regular “.thr” file needs to be
specified in the command line.
The syntax of the command is:
# sbcupdate -I kcs <path to change threshold file/filename>
The following is the example to change only selected thresholds using the change.thr
file:
# sbcupdate -I kcs change.thr
The output from this command should be similar to the following:
Changing thresholds settings.
Program exiting!
The change.thr file is a file of the same format as the regular .thr file created by the
sbcupdate tool when reading thresholds to a file. Each record in the .thr file should
begin with _SENSOR_NUMBER line followed by predefined THRESHOLDS lines. Only
thresholds listed in records are affected in SBC.
An example to change SBC Temp 1 Upper Non-critical thresholds is as follow:
Changing Thresholds Values via RMCP Bridging
For RMCP bridging to work correctly, the shelf manager must be connected to the
network in order to transmit TCP/IP traffic to and from the client. The user must also
specify the interface option to be “lan” for RMCP bridging.
To change the threshold values, the regular .thr file needs to be specified in the
command line.
1. Create a change.thr file with content as below:
2. Run the change threshold command.
3. Read the sensor threshold using a command as in
_SENSOR_NUMBER
_ACTIVE_UPPER_NON_CRITICAL_THRESHOLD
# sbcupdate -I kcs change.thr
Thresholds Using KCS Interface”
Temp 1 Upper Non-critical thresholds is changed to the value stated in the
change.thr file.
# sbcupdate -I kcs -M threshold --get-thr-factory
--get-thr-active --get-thr-sdr --get-thr -s 0x30
# cmmget -l blade12 -t "SBC Temp 1" -d thresholdsall
or
-P <password> -t <IPMB address> -M threshold
[--get-thr-factory] [--get-thr-active] [--get-thr-sdr]
[--get-thr] -s 0xYZ
-M threshold --get-thr-factory --get-thr-active
--get-thr-sdr --get-thr -s 0x93
) and add options to specify types of threshold to be read.
or the cmmget command to make sure the SBC
Intel NetStructure
Section 10.7.1, “Reading
®
: 30
: 45
MPCBL0050 Single Board Computer
Technical Product Specification
-M