F39-EU1E Omron, F39-EU1E Datasheet - Page 197

F3S-B OPTIONAL PROGRAMMING KIT

F39-EU1E

Manufacturer Part Number
F39-EU1E
Description
F3S-B OPTIONAL PROGRAMMING KIT
Manufacturer
Omron
Datasheet

Specifications of F39-EU1E

Leaded Process Compatible
No
Peak Reflow Compatible (260 C)
No
Light Curtain Type
Safety
Lead Free Status / RoHS Status
Contains lead / RoHS non-compliant
Lead Free Status / RoHS Status
Contains lead / RoHS non-compliant
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Fault Detection
When the G9SX-GS@ detects a fault, the ERR indicator and/or other indicators light or blink to inform the user about the fault.
Check and take necessary measures referring to the following table, and then re-supply power to the G9SX-GS@.
Safety Guard Switching Unit
indicator
Blinks
Lights
ERR
ED blinks
FB blinks
indicator
T1 blinks
T2 blinks
T6 blinks
T7 blinks
EI blinks
Other
---
http://www.ia.omron.com/
Fault due to electro-
magnetic disturbance or of
internal circuits.
Fault involved with safety
input A, channel 1
Fault involved with safety
input A, channel 2
Fault involved with safety
input B, channel 1
Fault involved with safety
input B, channel 2
Faults involved with
feedback/reset input
Fault in Expansion Unit
Fault involved with
instantaneous safety
outputs or logical AND
connection outputs
Fault involved with OFF-
delayed safety outputs
Fault
1) Excessive electromagnetic disturbance
2) Failure of the internal circuit
1) Failure involving the wiring of safety
2) Incorrect setting of cross fault detection
3) Failure of the circuit of safety input A
1) Failure involving the wiring of safety
2) Incorrect setting of cross fault detection
3) Failure of the circuit of safety input A
1) Failure involving the wiring of safety
2) Incorrect setting of cross fault detection
3) Failure of the circuit of safety input B
1) Failure involving the wiring of safety
2) Incorrect setting of cross fault detection
3) Failure of the circuit of safety input B
1) Failures involving the wiring of
2) Failures of the circuit of feedback/reset
1) Improper feedback signals from
2) Abnormal supply voltage to Expansion
3) Failure of the circuit of safety relay
1) Failure involving the wiring of
2) Failure of the circuit of Instantaneous
3) Failure involving the wiring of the logical
4) Failure of the circuit of the logical AND
5) Impermissible high ambient
1) Failure involving the wiring of OFF-
2) Incorrect set values for OFF-delay time
3) Failure of the circuit of OFF-delayed
4) Impermissible high ambient
input A channel 1
input
channel 1
input A channel 2
input
channel 2
input B channel 1
input
channel 1
input B channel 2
input
channel 2
feedback/reset input.
input
Expansion Unit
Unit
contact outputs
instantaneous safety outputs
safety outputs
AND connection output
connection output
temperature
delayed safety relay contact outputs
safety relay contact outputs
temperature
Expected causes of the fault
(c)Copyright OMRON Corporation 2007 All Rights Reserved.
1) Check the disturbance level around the
2) Replace with a new product.
1) Check the wiring to T11 and T12.
2) Check the wiring to Y1.
3) Replace with a new product.
1) Check the wiring to T21 and T22.
2) Check the wiring to Y1.
3) Replace with a new product.
1) Check the wiring to T61 and T62.
2) Check the wiring to Y2.
3) Replace with a new product.
1) Check the wiring to T71 and T72.
2) Check the wiring to Y2.
3) Replace with a new product.
1) Check the wiring to T31, T32 and T33.
2) Replace with a new product.
1) Check the connecting cable of Expansion Unit
2) Check the supply voltage to Expansion Unit.
Note: Make sure that all Expansion units' PWR
3) Replace the Expansion Unit with a new one.
1) Check the wiring to S14 and S24.
2) Replace with a new product.
3) Check the wiring to L1.
4) Replace with a new product.
5) Check the ambient temperature and spacing
1) Check the wiring to S44 and S54.
2) Confirm the set values of the OFF-delay time
3) Replace with a new product.
4) Check the ambient temperature and spacing
G9SX-GS@ and the related system.
and the connection of the terminating
connector
around the G9SX-GS@.
preset switches on the front and back of the
Unit.
around the G9SX-GS@.
Check points and measures to take
indicators are lit.
G9SX-GS
15

Related parts for F39-EU1E