When indicators other than the ERR indicator flash, check and take necessary actions referring to the following table.
(Expansion Unit)
indicator
indicator
indicator
Lights
Lights
ERR
ERR
ERR
Off
PWR flash
indicators
indicators
indicators
T1
T2
indicator
flashes
except
Other
Other
Other
AND
All
---
flash
http://www.ia.omron.com/
Fault involved with logical
AND connection input
Supply voltage outside the
rated value
Mismatch between input 1
and input 2.
Fault involved with safety
relay outputs of
Expansion Units
Fault
Fault
Fault
1. Error in the wiring of the logical AND
2. Incorrect setting for the logical AND
3. Failure of the circuit of the logical
1. Supply voltage outside the rated
The input status between input 1 and
input 2 is different, due to contact failure
or a short circuit of safety input
device(s) or a wiring fault.
1. Welding of relay contacts
2. Failure of the internal circuit
connection input
connection input
AND connection input
value
Expected causes of the fault
Expected cause of the fault
Expected cause of the fault
(c)Copyright OMRON Corporation 2007 All Rights Reserved.
1. Check the wiring to T41 and T42.
Note: 1. Make sure that the wiring length for the
2. Confirm the set value of the logical AND
3. Replace with a new product.
1. Check the supply voltage to the Units.
Check the wiring from safety input devices to the
G9SX. Or check the input sequence of safety input
devices. After removing the fault, turn both safety
inputs 1 and 2 to the OFF state.
Replace with a new product.
connection preset switch.
Check points and measures to take
Check points and measures to take
Check points and measures to take
2. Make sure that the logical AND
T41, T42 terminal is 100 meters or less.
connection signal is branched for 4 units
or fewer.
D40A/G9SX-NS
21